Working together!
Are you planning a data center for your customer?
We provide you with the tender documents for the entire technical
infrastructure for the construction of a server room, data center or IT security container.
Example text:
IT-SECURITY ROOM - ACCESS DOOR
Delivery and installation of an access door as a single door system.
The door hinge is to be DIN right or left.
Technical requirements for the door system:
- fire resistance min. F120
- smoke gas tightness according to DIN 18095 tested as system test
- fire water tightness according to EN60529 tested as system test
- min. IP54 - burglary protection WK IV according to EN1627 for the door system
Furthermore, the door system must be designed to resist pressure build-up
and mechanical attacks. Corresponding verifications are to be provided.
Equipped with:
Electric lock in accordance with EN 1300 prepared for activation by an access
control system provided by the customer, as well as potential-free contacts for
monitoring the door.
Surface treatment of the access door: Steel parts galvanized and primed.
The final painting is done in RAL / color according to the client.
Minimum dimensions (clear passage dimensions) / clear passage dimensions
(required, to be entered by the bidder)
Width: 1000 mm, height: 2100 mm, door leaf thickness: 60 mm
Installation drawings and the door construction must
be enclosed with the bid.
We will be pleased to support you with our know-how, even if it concerns
parts of IT security components.